Burner Controls Series IFD 244
Overvivew Spec
Mains voltage for grounded and ungrounded mains:
120 V AC, -15/+10%, 50/60 Hz,
230 V AC, -15/+10%, 50/60 Hz.
Safety time on start-...
Burner Controls Series IFS 110IM, IFS 111IM
Burner Controls Series IFD 244
Overvivew Spec
- Mains voltage IFS 110IM..T, IFS 111IM..T:220/240 V AC, +10/-15%, 50/60 Hz,
- Mains voltage IFS 110IM..N:110/120 V AC, +10/-15%, 50/60 Hz.
- Safety time: 2, 3, 5 or 10 s.
- Ignition time: Approx. 1, 2, 3 or 7 s.
- Power consumption: 9 VA.
- Output to ignition transformer with noswitchcontacts via semi-conductor.
- Output voltage for valves and ignition transformer= mains voltage.
- Contact rating:
Max. 1 A, cos ϕ = 0.3 per output:
Max. 1 A, cos ϕ = 1 per output,
Max. number of operating cycles: 250,000. - Total load: Max. 2 A.
- Reset button: Max. number of operating
- cycles: 1000.
- Input voltage signal inputs
- Rated value 110/120 V AC 220/240 V AC
- Signal “1” 80 – 126.5 V 160 – 264 V
- Signal “0” 0 – 20 V 0 – 40 V
- Frequency 50/60 Hz
สอบถามข้อมูลสินค้า โทร. 02-741-6200 E-mail: innothaiweb@innothai.com
-
-
Burner Controls Series BCU370 Overvivew Spec Para quemadores de gas modulantes de potencia ilimitadacon ventilador, en funcionamiento intermitente o continuo Control del ventilado...
-
Burner Controls Series IFD 450, IFD 454 Overvivew Spec Mains voltage for grounded and ungroundedmains:IFD..T: 220/240 V AC, -15/+10%, 50/60 Hz, IFD..N: upon request110/120 V AC, -...